Bore not starting Booragoon 

We had installed a bore for Bob in Booragoon a few years ago. 

He rang to say the bore was not working. We sent out our specialist bore electrician Dave. The submersible pump motor tested ok and he noted that there was no 24 volt to relay from controller. 

He found that there was a red multicore running along the pavers from below the reticulation controller to below the bore start box. The joint connection at the bottom of the start box was faulty so he remade it. 

All working again on front 2 stations. There was no cover on station 3,4,5 and 6, it was cut off due to construction. He fixed. 

We have drilled and repaired many bores in the Booragoon area and surrounding suburbs of Mount Pleasant, Myaree and Melville. If you have a problem with your Booragoon bore call Troy on 92460111 or go to our website HERE

Bore Automation Perth

We are automating an old bore in the southern Perth suburb of Shoalwater. 

As pictured it is an old style well with a tin lid. 

The sprinkler system is currently manually operated with five inground gate valves. This is common with these older style Perth water bores.

We will replace manual valves with 24  V solenoid valves which will be wired into a new reticulation controller. Our electrician will do the interface to start the bore automatically via a 24 V relay. 