Tag Archives: bore

Bore Repair Greenwood

Bore problem Greenwood

Pat lives in Greenwood and her RCD (Residual Current Device) switch was tripping.  (It was the RCD rather than the circuit breaker tripping ) Who did she call? Us on 9246 0111.

We sent out our experienced bore electrician, Dave.

The first thing he did was test the submersible water bore motor and it tested OK. There was one RCD that protected all power points on two circuits with the pump on the power circuit.

We fixed RCD that was tripping while retic being used
A customer’s RCD was tripping when she was using her retic

Bore was tripping when retic ran.

Pat told us that when station 3 was on the RCD tripped. Dave noticed there was a broken sprinkler right near the bore head washing out sand.

img_9208-1

He exposed the bore head and it was filled with sand which he dug out by hand. Sand should not cover the top of a submersible bore for a variety of reasons. It can drop down inside the bore casing and as it is pumped back out it will prematurely wear  out the pump impellers. It can also play havoc with solenoid valves in the retic system.

But why was this bore tripping?

As Dave dig down he exposed the electrical junction box that joined the cables up from the pump with those going towards the house. It appears that as the sand got wet from the broken sprinkler the moisture was getting in to the less than perfect electrical junction box and causing the bore RCD to trip. Upon removing the sand and retesting all worked OK.  It has been noted though that the j box will need replacing and raising whenever the submersible motor is replaced.

img_9204
Submersible Bores should never be covered by sand

This Greenwood garden bore and retic system is now working OK.

Can we help you repair your modern submersible water bore? Call us on 9246 0111 or book a bore Repair here

Bore Repair Lockridge

We have nearly 20 years experience in installing, repairing and servicing water bores in the Perth Metropolitan area. This means we have a depth of knowledge and experience to tackle any challenge.

Reticulation Connection in Lockridge

BUT not all bore connections are as hard as this one in Lockridge!

Connect new bore to older reticulation connection
Lockridge reticulation has to be connected to new bore

Our client was a church in Lockridge. We drilled a modern submersible water bore replacing their old style well with a tin lid.

Jack disconnected this retic system from the old bore and connected it to the new submersible bore we have just drilled.

As you can see all the fittings were waist deep in an old pit. Not pretty but nice work Jack!

Lockridge water bore connection to reticulation
Connection of old reticulation system to new water bore

So anywhere in the area Lockridge, Eden Hill or Kiara if you your water bore needs repair or you would like a new submersible water bore, call us on 9246 0111 or go to our website here

Gravel Packing Water Bore

 

To safeguard the construction of a modern submersible water bore in the Perth metropolitan area water bores should be gravel packed. Read more about gravel packing water bores HERE

To help keep sands and silts out of a modern domestic water bore we use driller’s gravel. Gravel packing a modern submersible water bore is an important part of good bore construction.

If you have been thinking about a Perth water bore to save money and have the best garden in the street call us on 9246 0111

My submersible pump running with no water

My submersible pump running with no water

My submersible pump running with no water


— Read on waterboretroubleshootersperth.com/2013/09/14/i-know-my-submersible-pump-is-running-but-no-water/

Bore Not Starting Tapping

Mark from Tapping phoned us on 9246 0111 to say his bore was not working.

We sent our specialist bore electrician Dave to test the single phase two wire motor which tested OK. Good news!

Borehead of Tapping water bore
Top of Tapping water bore

He found the 24 volt relay was faulty and replaced it for new. All is working again on 3 stations with all readings OK.

Tapping water bore repaired
Tests OK after relay replaced

If you live in the Tapping area or the surrounding suburbs of Wanneroo, Banksia Grove or Joondallup and your modern submersible water bore or old well is not working and needs repair call us on 9246 0111

FYI (source Wikipedia)

Tapping is a suburb of Perth, Western Australia, located within the City of Wanneroo. It came into being in the early 1990s as a subdivision of Wanneroo, originally as part of the Carramar estate. Tapping was chosen as the suburb name in honour of an early settler family in the Wanneroo area. Mr William Tapping arrived in 1886 and Molly and Dolly Tapping were long time Postmistresses in Wanneroo. The name for the suburb was approved in 1997.

Repair Old Well Queens Park

Dave our specialist bore electrician attended a job in Queens Park where it was reported the centrifugal pump for an old well wasn’t working.

The single phase Davey Boremaster tested OK so he replaced the 30 mf capacitor for new and the water bore is working again.

img_7425.jpg

However he did note on his report that there were distinct mechanical sounds and he was not sure how long the pump would last before it fails mechanically.

If your old well water bore needs repair and you are in Queens Park or the surrounding areas of Welshpool, Cannington or Bentley call us on 9246 0111 or check out our website

Repair Water Bore Trigg

The modern submersible water bore at property in the Perth coastal suburb of Trigg wasn’t working.

The reticulation controller seemed normal and the green light on side of bore start box was still coming on. Nothing tripping in meter box.

The man for the job was Dave, our bore electrician, who has been solving these sorts of mysteries for years.

He tested everything and found the fault with the illuminated green rocker switch on the bore control box

He isolated it and this Trigg modern submersible water bore and the reticulation now working with crystal clear water.

 

If your water bore needs repair call us on 9246 0111 or we will call you

Fix Old Bore Yangebup

One of our recent bore repair jobs was a centrifugal pump motor tripping the circuit breaker in the backyard of this property in Yangebup. You can see the rusted and partially collapsed tin lid of the bore well in this picture.

Bore safety

As an aside it reminded us all old style bore well lids should be secured. Take a look here on bore safety.

Tin lid of old well in backyard of a property in Yangebup
Yangebup old bore needs fixing

Dave, our specialist bore and pump electrician attended the job and found there was a 3 liner well with bore pump located on wooden boards 2 liners down.

Fix 3 liner well Yangebup
3 liner  bore well Yangebup

 

Pump failed mechanically

The 3 phase pump and motor had failed mechanically and was just humming. The pump had not fused and was fine electrically but need replacement.

We returned and supplied and installed a 2.2 kW 3 phase centrifugal pump and fittings.

Our customer now has bore water again.

Mobile bore repairs

If you are in Yangebup or the surrounding areas of South Lake, Bibra Lake or Spearwood and your old bore well needs repair call us on 9246 0111 or book your repairs here

Bore Repair Armadale

Patrick from Armadale rang us on 9246 0111 when his submersible pump motor was not working.

We sent our specialist bore electrician, Dave.

Bore control in roof space

The Franklin Electric 1.5 kW  single phase bore pump start box was in the roof space with 24 volt relay behind meter box panel. This is a very unusual place to find the bore  controls as the start box contains the capacitor and overload circuits. Also unorthodox place to position the 24 volt relay that accepts the start signal from the retic controller.

Pump running but no water

The pump motor was running but only drawing 7.7amps which is more consistent with  a 1.1kW not a 1.5kW submersible pump motor.

Top of submersible bore under lawn

Dave exposed the bore head which was located in the front lawn. The top of the bore was just under the lawn with the typical green lid. There was no barrel union (threaded coupling) so he drilled a small hole in the top of the PVC pipe connected to the retic system and found there was no water in it as would be normal. This could signify a check valve failed in the pump or a blown poly line that brings the bore water to the surface.

Return to pull out submersible pump

Our next step will be to winch up the pump motor to investigate further and then repair this Armadale water bore. Our submersible pump winch team is booked to return.

If you are in the Armadale area or any Perth suburb and your water bore needs repair call us on 9246 0111 or book your bore repair here

Best Motor for Water Bore Perth

We repair or replace all brands of submersible bore pumps.

We are proud to be able to use genuine Italian PM Technology motors compatible with all standard submersible 4″ pumps.

PM Technology Motor - 2

It is a robust and well-engineered stainless steel submersible motor that is well suited for Australian down bore-hole conditions.

For a good detailed read on the PM Technology motors check out HERE

PM Technology Motor - 3

If your bore needs fixing call us on 9246 0111 – 7 days for prompt onsite attention in any Perth suburb. We also fix old wells and centrifugal bore pumps.